How to select MCCB or MCB for Motor ?
The selection depends upon the starting method
1 . In case of DOL starting method , we have to chose the MCCB rating 2 - 3 times of the rated motor current rating ( Because motor draw 3-5 times of current than the rated current at starting )
2 . In case of STAR_DELTA or VFD , then we have to choose the MCCB rating 1.5 times of the rated motoe current rating .
Reason :
* Why we are selecting the MCCB rating greater than the actual motor current rating means that in case of full load the MCCB will be running in full load current so there are possibility to trip . so we are increasing the rating of the MCCB so that it can run in its 70-80 % of the rated current .
* MCCB's and MCB's are not designed for motor protection . You need to use OLR
( Over Load Relay ) or MPCB ( Motor Protection Circuit Breaker ) .
circuit breaker selection for induction motor
ReplyDeleteCircuit breaker is better than fuse
ReplyDeleteIt's really nice and meanful. it's really cool blog. Linking is very useful thing.you have really helped lots of people who visit blog and provide them usefull information. Fault Location Services Morningside
ReplyDeleteThis type of message always inspiring and I prefer to read quality content, so happy to find good place to many here in the post, the writing is just great, thanks for the post. Wohnmobilvermietung Elmshorn
ReplyDeleteStill my motor is 55kw 3phase . Can I use 125 Amps MCCB ....
ReplyDeleteMotor load current is 96Amps